Need to connect M-Bus and BACnet? The Weble WBox routes M-Bus BACnet natively: one gateway speaks both protocols and maps data points in real time — no PC, no middleware, no cloud dependency.
M-Bus reads heat, water, gas and electricity meters over a dedicated 2-wire bus.
M-Bus driver →BACnet (BACnet/IP, MS/TP) is the standard for building management systems and HVAC supervision.
BACnet driver →Further reading: Wired vs wireless M-Bus: what is the difference? →
A BACnet BMS needs the meter data sitting on an M-Bus loop — district heating, cold and hot water, electricity sub-meters. Instead of a separate metering concentrator and a manual export, the WBox exposes each M-Bus meter as BACnet objects the BMS reads directly. This is the standard path for tenant billing, ESG and consumption reporting in commercial and multi-tenant buildings, with every reading time-stamped and trended in the same system.
Activate the BACnet and M-Bus drivers. The WBox polls the M-Bus meters on a schedule, reads the records you select (energy, volume, power, flow and return temperatures) and maps each to a BACnet Analog Input with the correct unit and COV increment. The BMS then polls them like any native point. A JavaScript step can derive values — for example turning a kWh index into instantaneous power — before they appear on BACnet.
A worked example, all on one gateway:
#3 energy (kWh) → BACnet Analog Input 30#3 volume (m³) → BACnet Analog Input 31#3 flow temperature (°C) → BACnet Analog Input 32On the WBox, a driver licence enables the whole protocol — there is no artificial per-point tier to unlock. Capacity scales with the gateway model, from the compact S103 to the E413: you are bounded by the field bus, not by your licence.
With a WBox gateway running the M-Bus and BACnet drivers: it reads the M-Bus meters and exposes each reading as a BACnet/IP object, with no intermediate PLC.
The gateway can scan secondary and primary meter addresses directly from the web interface.
For wired M-Bus, yes: a level converter (RS485toMBus or EthernettoMBus) powers the bus and adapts it to the gateway. For Wireless M-Bus, a radio stick is enough.
Meter reading is read-only. On the same gateway, the WBox can also route BACnet setpoints to other protocols (Modbus, KNX) if the project requires it.
From several dozen to several hundred, depending on the converter (slave count) and the gateway model. Polling and caching are configurable to protect the bus.
One WBox gateway with these two driver licences:
Find the right WBox gateway for your installation, or get in touch to validate your case.
Configure my gateway© 2026 Weble Sàrl. All rights reserved. General conditions