Need to connect Modbus and BACnet? The Weble WBox routes Modbus BACnet natively: one gateway speaks both protocols and maps data points in real time — no PC, no middleware, no cloud dependency.

Modbus to BACnet gateway

The protocols

Modbus

Modbus (TCP/IP and RTU) connects PLCs, meters, variable-speed drives and countless industrial devices.

Modbus driver →

BACnet

BACnet (BACnet/IP, MS/TP) is the standard for building management systems and HVAC supervision.

BACnet driver →

Typical use case

One of the most common retrofits: the BMS speaks BACnet/IP, but chillers, heat-meters, variable-speed drives, inverters and PLCs on site only speak Modbus. Replacing them is out of the question. The WBox integrates that field equipment into the BMS so it shows up as native BACnet — read and written from existing graphics, schedules and trends — and you extend an existing supervision system instead of bolting a second one beside it.

In the field

Weble customers run this routing in production:

How the WBox bridges Modbus and BACnet

Activate the BACnet and Modbus drivers. Modbus holding and input registers map to BACnet objects: measurements to Analog Input/Value, states and commands to Binary Input/Value. The WBox handles scaling, word and byte order, and signed values per register, and exposes the result as discoverable BACnet objects — no per-point setup on the BMS side. Writes from BACnet propagate to Modbus holding registers, and a JavaScript step can clamp, scale or combine values before they cross.

Example mapping

A worked example, all on one gateway:

  • Modbus holding 40001 active power (×0.1 kW) → BACnet Analog Input 20
  • Modbus input 30005 run status → BACnet Binary Input 3
  • BACnet Analog Value 8 setpoint → Modbus holding 40010

Capacity & limits

  • Modbus — Modbus addresses up to 247 slaves per line (RTU or TCP) — about 32 RTU devices per RS-485 segment before a repeater.
  • BACnet — BACnet/IP scales to large object counts; BACnet MS/TP carries up to 127 master nodes per segment.

On the WBox, a driver licence enables the whole protocol — there is no artificial per-point tier to unlock. Capacity scales with the gateway model, from the compact S103 to the E413: you are bounded by the field bus, not by your licence.

Frequently asked questions

How do I expose a Modbus device in a BACnet BMS?

A WBox gateway with the Modbus and BACnet drivers reads the Modbus registers (RTU or TCP) and exposes them as native BACnet/IP objects, with no intermediate PLC.

Are Modbus RTU and Modbus TCP both supported?

Yes, both: Modbus RTU over RS485 and Modbus TCP/IP, as master or slave, on the same gateway.

Is the Modbus ⇄ BACnet bridge bidirectional?

Yes: the BMS reads the Modbus registers and can also write a BACnet setpoint pushed back into a Modbus register.

Do I need a vendor-specific gateway?

No: the drivers are licence-activated on a single WBox gateway, with no proprietary hardware or intermediate PLC.

What you need

One WBox gateway with these two driver licences:

Route Modbus BACnet on your project

Find the right WBox gateway for your installation, or get in touch to validate your case.

Configure my gateway