Need to connect Modbus and BACnet? The Weble WBox routes Modbus BACnet natively: one gateway speaks both protocols and maps data points in real time — no PC, no middleware, no cloud dependency.
Modbus (TCP/IP and RTU) connects PLCs, meters, variable-speed drives and countless industrial devices.
Modbus driver →BACnet (BACnet/IP, MS/TP) is the standard for building management systems and HVAC supervision.
BACnet driver →One of the most common retrofits: the BMS speaks BACnet/IP, but chillers, heat-meters, variable-speed drives, inverters and PLCs on site only speak Modbus. Replacing them is out of the question. The WBox integrates that field equipment into the BMS so it shows up as native BACnet — read and written from existing graphics, schedules and trends — and you extend an existing supervision system instead of bolting a second one beside it.
Activate the BACnet and Modbus drivers. Modbus holding and input registers map to BACnet objects: measurements to Analog Input/Value, states and commands to Binary Input/Value. The WBox handles scaling, word and byte order, and signed values per register, and exposes the result as discoverable BACnet objects — no per-point setup on the BMS side. Writes from BACnet propagate to Modbus holding registers, and a JavaScript step can clamp, scale or combine values before they cross.
A worked example, all on one gateway:
40001 active power (×0.1 kW) → BACnet Analog Input 2030005 run status → BACnet Binary Input 3Analog Value 8 setpoint → Modbus holding 40010Find the right WBox gateway for your installation, or get in touch to validate your case.